Improvement and Simulation of Bypass Circuit Breaker Protection for UHVDC Transmission System

Xilin YAN , Qianjin WU , Jianbao GUO , Xuezhi WANG , Baoquan GU

›› 2017, Vol. 11 ›› Issue (12) : 9 -15.

PDF
›› 2017, Vol. 11 ›› Issue (12) : 9 -15. DOI: 10.13648/j.cnki.issn1674-0629.2017.12.002
research-article

Improvement and Simulation of Bypass Circuit Breaker Protection for UHVDC Transmission System

Author information +
History +
PDF

Abstract

Combined with the principle of bypass switch protection stage 1 (82BPS-1), the action reason and existing risk of 82BPS-1 protection in Puer-Qiaoxiang UHVDC on September 10 of 2015 is analyzed. Then the defect of bypass switch protection is found that the unreasonable integral counting module can make 82BPS-1 protection maloperation. Aiming at the problem, an improved measure is proposed which using the bypass switch closing order to clear the count of 82BPS-1 protection integral counting module. The effectiveness of the measure has been verified by RTDS simulation tests. At present, the improved measure has been applied to Puer-Qiaoxiang and Chuxiong-Suidong UHVDC transmission systems.

Keywords

UHVDC / control and protection system / protection maloperation / bypass switch protection

Cite this article

Download citation ▾
Xilin YAN,Qianjin WU,Jianbao GUO,Xuezhi WANG,Baoquan GU. Improvement and Simulation of Bypass Circuit Breaker Protection for UHVDC Transmission System. 2017, 11(12): 9-15 DOI:10.13648/j.cnki.issn1674-0629.2017.12.002