Lightning Protection Performance of 500 kV Double-Circuit Transmission Lines on the Same Tower with Composite Cross-Arm

Li TANG , Lei LIU , Guoli WANG , Xiaolin LI , Donggen LIU , Yigang MA

›› 2019, Vol. 13 ›› Issue (9) : 25 -30.

PDF
›› 2019, Vol. 13 ›› Issue (9) : 25 -30. DOI: 10.13648/j.cnki.issn1674-0629.2019.09.005
research-article

Lightning Protection Performance of 500 kV Double-Circuit Transmission Lines on the Same Tower with Composite Cross-Arm

Author information +
History +
PDF

Abstract

Composite cross-arms have been used in 35—1 000 kV transmission lines. However the researches on lightning protection performance of the composite cross arm tower are less. Thus, voltage/time curve for 500 kV transmission line tower with composite cross-arm are measured under positive and negative lightning impulses at the Kunming National Engineering Laboratory for UHV Engineering Technology. Flashover criterions of composite cross-arm are obtained. According to the parameters of actual double-circuit transmission line tower with composite cross-arm, electromagnetic transient model of double-circuit transmission lines has been established. Lightning withstand level of back-flashover and shielding strike for double-circuit transmission lines on the same tower with composite cross-arm are calculated using the improved flashover criterion. The results show that the calculated back-flashover lightning withstand level of composite cross-arm tower is about 4% higher than it of conventional tower with the same parameters. The shielding failure lightning withstand level of composite cross-arm tower and conventional tower are similar. Based on the voltage/time curve experimental results, the coefficient k and E0 for the positive velocity of the leader formula of composite cross-arm are modified to 0.50×10-6 m2/(V2·s) and 600 kV/m respectively. and the coefficient k and E0 for negative velocity of the leader formula are modified to 0.55×10-6 m2/(V2·s) and 650 kV/m respectively. The improved leader propagation models are suitable for research of lightning performance of transmission line tower with composite cross-arm.

Keywords

composite cross-arm / double-circuit lines on the same tower / flashover criterion / voltage/time curve / lightning withstand level

Cite this article

Download citation ▾
Li TANG,Lei LIU,Guoli WANG,Xiaolin LI,Donggen LIU,Yigang MA. Lightning Protection Performance of 500 kV Double-Circuit Transmission Lines on the Same Tower with Composite Cross-Arm. 2019, 13(9): 25-30 DOI:10.13648/j.cnki.issn1674-0629.2019.09.005

登录浏览全文

4963

注册一个新账户 忘记密码

References

PDF

8

Accesses

0

Citation

Detail

Sections
Recommended

AI思维导图

/