Reliability Analysis of Tower-Line Structure of Transmission Line Under Combined Ice-Wind Condition

Tianru SHI , Danhui HU , Xueming ZHOU , Yaodong ZHANG

›› 2019, Vol. 13 ›› Issue (10) : 81 -86.

PDF
›› 2019, Vol. 13 ›› Issue (10) : 81 -86. DOI: 10.13648/j.cnki.issn1674-0629.2019.10.011
research-article

Reliability Analysis of Tower-Line Structure of Transmission Line Under Combined Ice-Wind Condition

Author information +
History +
PDF

Abstract

In this paper, the reliability of transmission line tower-line structure system under combined ice-wind condition is modeled and analyzed. Firstly, the reliability indices of pole-tower structure, insulator, fittings and grounding wire are calculated by checking point method of first-order second-moment method. Then, the reliability calculation method of series structure system is used to calculate pole-tower structure, insulator, fittings and grounding wire. Finally, taking a 220 kV straight tower and tension tower as examples, the system reliability indices of pole-tower structure, insulator, fittings and ground wire under combined ice-wind condition are calculated and analyzed, which can provide reference and guidance for disaster prevention of transmission lines.

Keywords

combined ice-wind / series structure system / checking point method / reliability / transmission line

Cite this article

Download citation ▾
Tianru SHI,Danhui HU,Xueming ZHOU,Yaodong ZHANG. Reliability Analysis of Tower-Line Structure of Transmission Line Under Combined Ice-Wind Condition. 2019, 13(10): 81-86 DOI:10.13648/j.cnki.issn1674-0629.2019.10.011

登录浏览全文

4963

注册一个新账户 忘记密码

References

Funding

the Key Science and Technology Project of State Grid Corporation of China(52170217000U)