Influence and Countermeasures of Inrush Current of Transformer with Built-in High Voltage Winding on Zero Sequence Overcurrent Protection of Bus Tie Circuit-Breaker
Hanli WENG , Tao KANG , Yida GUO , Yongbo JIA , Zhenxing LI , Jingguang HUANG
›› 2023, Vol. 17 ›› Issue (3) : 75 -84.
Influence and Countermeasures of Inrush Current of Transformer with Built-in High Voltage Winding on Zero Sequence Overcurrent Protection of Bus Tie Circuit-Breaker
The problem of inrush current becomes more prominent by changing the arrangement order of the inner windings of the transformer with built-in high voltage winding. The zero-sequence over-current protection of bus tie circuit-breaker is faced with a high risk of maloperation because of the high amplitude zero-sequence inrush current due to the unloaded transformer energizaiton, which threatens the safe operation of the power grid. Combining with the setting principle of zero-sequence overcurrent protection of bus tie circuit-breaker, the maloperation mechanism of the protection under inrush current conditions of unloaded energization of the transformer with built-in high voltage winding is revealed in this paper. Based on the difference of waveform characteristics between zero-sequence inrush current and fault zero-sequence current, and considering the influence of saturation of current transformer (CT), the restraint criterion of zero-sequence overcurrent protection against maloperations applying the variation characteristics of symbol sequence of zero-sequence current is proposed. The maloperation mechanism of the protection and the validity of the proposed criterion are verified by simulation tests.
transformer with built-in high voltage winding / current transformer saturation / zero-sequence inrush current / variation characteristics of symbol sequence / zero-sequence overcurrent protection
the National Natural Science Foundation of China(52077120)
/
| 〈 |
|
〉 |